Lifting platforms on the steel structure of Terminal 4 at Madrid-Barajas during the installation of passive fire protection systems

Passive Fire Protection Systems

Intumescent paints and coatings, sprayed mortars, rigid panels, and sealed fire barriers—our passive fire protection systems are all guided by the same principle: the system is chosen based on the building component, not the other way around.

Terminal 4 Under Construction · Adolfo Suárez Madrid-Barajas Airport

Intumescent paints and coatings

Metal roof trusses and purlins coated with intumescent paint, one of the passive fire protection systems

Intumescent paint for metal structures

It is applied mechanically using a low-pressure airless sprayer; in exceptional cases, it may be applied with a brush or roller. When exposed to heat, it expands in volume and insulates the steel. It remains stable up to 30' without significant additional cost; beyond that, the thickness—and the cost—increase with the cross-sectional area of the profile.

See this solution in a real-world application →
Metal beams and columns for industrial buildings, primed and coated with white fire-retardant enamel

Fire-retardant primers and topcoats

Two-component synthetic and epoxy fire-retardant primers compatible with intumescent systems; the epoxy can even be applied over existing primers or enamels, acting as a bonding coat. Fire-retardant enamels seal the system against atmospheric agents and are available in any color.

Featured Project: University of Málaga →

Protective Mortars

Metal columns and beams primed red and coated with fire-resistant mortar sprayed on site
Perlite-vermiculite base

Vermiculite Mortars

CompositionCalcium sulfate, perlite, vermiculite, and additives
ApplicationMechanical, with the option of manual smoothing
Density450–650 kg/m³
R and REIUp to 240'

Excellent adhesion to primed or unprimed steel, galvanized sheet metal, and concrete. No metal mesh is required, except on wood. Installed at the El Mirador Shopping Center (Cuenca) and the Tenerife Sur Convention Center, among other locations.

Rock wool base

Rock Wool Mortars

CompositionRock wool, cement, and additives
ApplicationMechanical, with grinding or surface hardening
Density300–800 kg/m³
R and REIFrom 30' to 240', depending on thickness and mass

In addition to fire protection, it provides thermal insulation and improves sound quality through sound absorption. It has been installed at Los Rodeos Airport (Tenerife) and at logistics centers such as the Mercadona facility in Ciempozuelos.

Fire-Resistant Panels and Partitions

Installation of fire-resistant panels—one of our passive fire protection systems—on the curved suspended ceiling at Los Rodeos Airport in Tenerife

Rigid calcium silicate fiber panels

Used alone or in combination with rock wool, they protect metal structures up to R-240, ventilation ducts, and electrical conduits. They are also used for partitioning with drywall, as a suspended ceiling to protect floor slabs, and at the junction between floor slabs and curtain walls. Smooth finish, suitable for painting.

Featured Project: Los Rodeos Airport →
Concrete lattice slab protected with sprayed ablative ceramic

Ablative Ceramics for Floor Slabs

Apply mechanically using a low-pressure airless sprayer; in exceptional cases, apply with a brush or roller. Density ranges from 1,200 to 1,300 kg/m³ and achieves REI-180 on floor slabs depending on the required equivalent thickness. Excellent adhesion to clean surfaces free of form release agent residue.

Featured Project: Nervión Plaza →

Sealing and Compartmentalization

Intumescent pipe collars installed where two PVC pipes pass through a wall, providing a fire-rated seal

Sealing Penetrations and Installations

Intumescent collars and wraps for PVC pipes, pads for installation openings, intumescent silicone for small openings, and non-shrink mortars or rock wool panels with silicone for larger openings.

Featured Project: Área Sur Shopping Center →
Expansion joint between the floor slab and the wall, sealed to prevent the spread of fire

Expansion joints and roofs

Sealing of structural expansion joints and linear meters of separation on the roof between different fire compartments, preventing the spread of fire between compartmentalized areas.

Featured Project: Barajas Terminal 4 →

Regulations and Testing

Each system is certified through testing, not through a product data sheet. These are the standards that govern our work:

UNE 23820/97Fire resistance (Spanish standard)
EN ENV 13381-4Fire resistance (European standard)
EN ENV 13381-3 / 13381-5Fire Resistance of Floor Slabs, Walls, and Composite Sheeting
Royal Decree 312/2005 · EN 13501-1Fire Reaction Classification
EN 1992-1-2 / EN 1993-1-2Eurocodes for Concrete and Steel Structures Resistant to Fire